The EncryptorPak Z is equipped with wireless ZigBee© to provide secure Ethernet-to-serial
and serial-to-serial “over the air” connections between MTU and RTUs. The unit encrypts
and tunnels serial DNP3 or Modbus data and its operation requires no change to your
network or applications.
Overview ▲Top
IEEE 1711-2010 standard for cyber security of substation serial links
- AES encryption, HMAC authentication
- Key management (2 -level)
- Modbus RTU/ASCII, DNP3
- Point-to-point (P2P) & multipoint operation
- Asynchronous 300 to 115 Kbps
Wireless
- Frequency: 2.4 Ghz
- RF Range: 1 mile (line of sight)
Plus Secure Ethernet-to-serial and serial-to-serial “over the air” connections
Plus Multi-protocol support
- AES (8-bit CFB) in P2P for Allen-Bradley DF-1, Bristol BSAP, Fisher ROC & more
Plus 3-in-1 software-configurable ports
Plus Up to 200 secure tunnels
- Each tunnel has its own encryption key and protects one or group of RTUs
Plus Web interface for easy configuration & management
- Access is controlled by three separate roles: admin, security officer, and operator
Benefits ▲Top
Cost-effective
- No change to existing software or equipment
Improves security posture
- By easily defining and deploying policy-based security across serial links
Quickly integrates into existing network
- “Bump-in-the-wire” security for serial DNP3, Modbus, and others
- Supports mixed encrypted and clear traffic for seamless operation
Flexible configuration
- Any mix or match of RS-232, RS-422, or RS-485 (2- or 4-wire) interfaces via DB-9
or terminal block
- Supports point-to-point and multi-point
Conforms to NERC CIP audit logging
- Multi-role access control with system activity logging
Specs ▲Top
Standards
- IEEE 1711-2010 Standard for a Cryptographic Protocol for Cyber Security of Substation
Serial Links
Cryptographic Suites
- Advanced Encryption Standard (AES) 128-bit
- MD5 128-bit hash (RFC 1321)
- SHA-1 160-bit hash (ANSI X9.30-2 and FIPS 180-1)
Simultaneous Secure Tunnels
Encryption Keys
- Automated rekey of data key
- Two-level key management:
- Key Encrypting Key
- Data Key (unique for tunnel)
Topologies
- Point-to-point (P2P)
- Point-to-multipoint
Protocols
Serial-to-Serial
- DNP3
- Modbus RTU
- Modbus ASCII
- Any byte-oriented protocol in P2P
Ethernet-to-Serial
- Modbus TCP and UDP
- Modbus RTU/ASCII Over TCP and UDP
- DNP3 Over TCP
Frequency/RF Range
Interfaces
- LOCAL: 10-pin terminal block & DB9 female (RS-232/422/485)
- REMOTE: ZigBee®* wireless antenna
* ZigBee is a worldwide open standard for wireless
radio networks in the monitoring and control fields - MGMT: DB9 female (RS-232)
- LAN: RJ45 Ethernet (10/100BaseT)
Web Interface
- 3-level, role-based, password protected login
LED Indicators
- Power
- Ethernet Activity
- Secure Link Activity
Power
Physical
- Enclosure: 18 gauge steel
- Weight: 1 lb
- Size: 1 x 8 x 5 inches (2.54 x 20.32 x 12.7 cm)
Operating Environment
- -40° C to 85° C (-40° F to 185° F)
Green Technology
- Low-power
- All components are RoHS compliant
Warranty